| IBC Section 716 |
Opening Protectives — fire doors, fire windows, fire shutters. Governs where fire-rated glazing can be used, maximum glass area per assembly type, and rating required by occupancy separation. |
ACG uses IBC 716 to confirm product selection is appropriate for the fire-resistance rating required by the building's occupancy separation table (IBC Table 716.5). |
| NFPA 80 |
Standard for Fire Doors and Other Opening Protectives. Installation requirements, hardware requirements, clearances, and field testing procedures for fire-rated door assemblies. |
ACG installs fire-rated door assemblies per NFPA 80 clearance requirements. Positively latching hardware, door closers, smoke gaskets per NFPA 80 Section 4.8. |
| NFPA 252 |
Standard Methods of Fire Tests of Door Assemblies. The test method used to achieve a UL label on a fire-rated door assembly. |
ACG installs only tested assemblies with valid UL labels. No field modifications to frame, glass size, or hardware that would invalidate the NFPA 252 tested assembly. |
| UL 9 |
Fire Tests of Window Assemblies. Test method for fire windows, fire-rated glazing in frames other than door assemblies. |
ACG installs fire-rated window assemblies (sidelites, corridor windows, partition glass) with UL 9 listed configurations. Glass size, frame anchorage, and glazing method per the UL listing. |
| IBC Chapter 7 |
Fire-Resistance-Rated Construction. Occupancy separation requirements, fire-resistance ratings, and where fire-rated assemblies are required by occupancy type and building height. |
ACG coordinates with the EOR and architect to confirm the required rating for each opening before product selection. A 20-minute door in a 2-hour separation wall is a code failure ACG prevents upstream. |